PLUG FAN HEAT RECOVERY DEVICES
CH-VAMP
In schools, hospitals, shopping malls, villas, etc. It is designed for ventilation without heat loss. High efficiency heat recovery heat exchangers in the devices is used. Thanks to these Heat Exchangers, the fresh air preheating in winter conditions without spending extra energy, summer conditions, pre-cooling and maintaining the existing heat ventilation of the environment is carried out.
Technical Information
| Model | Voltaj Voltage (v) | Güç Power (w) | Debi Air Flow (m³/h) | Filtre Filter | Devir Speed (rpm) | Ses Seviyesi Noise Level (dB(A)) |
|---|---|---|---|---|---|---|
| CH-VAMP 250 | 230 | 2 x 200 | 750 | G4 | 2800 | 48 |
| CH-VAMP 280 | 230 | 2 x 250 | 1000 | G4 | 2800 | 56 |
| CH-VAMP 315 | 230 | 2 x 140 | 1500 | G4 | 1400 | 66 |
| CH-VAMP 355 | 230 | 2 x 220 | 2000 | G4 | 1400 | 68 |
| CH-VAMP 400 | 230 | 2 x 560 | 3000 | G4 | 1400 | 74 |
| CH-VAMP 450 | 230 | 2 x 750 | 4000 | G4 | 1400 | 78 |
| CH-VAMP 500 | 230 | 2 x 1250 | 5000 | G4 | 1400 | 86 |
ASK PRICE
| Model | A | B | C | D | E |
|---|---|---|---|---|---|
| CH-VAMP 250 | 940 | 360 | 1140 | 210 | 230 |
| CH-VAMP 280 | 940 | 360 | 1140 | 210 | 260 |
| CH-VAMP 315 | 940 | 420 | 1350 | 300 | 320 |
| CH-VAMP 355 | 1000 | 450 | 1550 | 360 | 400 |
| CH-VAMP 400 | 1150 | 500 | 1750 | 360 | 400 |
| CH-VAMP 450 | 1150 | 575 | 1750 | 360 | 400 |
| CH-VAMP 500 | 1250 | 620 | 1950 | 360 | 400 |
ELECTION TABLE
| Model | Pa | 0 | 50 | 100 | 200 | 300 | 400 |
|---|---|---|---|---|---|---|---|
| CH-VAMP 250 | m3/h | 750 | 710 | 650 | 450 | 200 | - |
| CH-VAMP 280 | m3/h | 1000 | 920 | 850 | 700 | 530 | 250 |
| CH-VAMP 315 | m3/h | 1500 | 1400 | 1300 | 1000 | 700 | - |
| CH-VAMP 355 | m3/h | 2000 | 1850 | 1730 | 1360 | 920 | - |
| CH-VAMP 400 | m3/h | 3000 | 2850 | 2500 | 1900 | 1450 | - |
| CH-VAMP 450 | m3/h | 4000 | 3800 | 3300 | 2600 | 2000 | 1000 |
| CH-VAMP 500 | m3/h | 5000 | 4700 | 4200 | 3300 | 2700 | 1800 |
TECHNICAL DIMENSIONS